VMS36-1 – 36 kV voltage transformer

Instrument voltage
transformers, indoor,
Cast-Resin Insulated
Technical data
Type
VMS36-1
Highest voltage for equipment
kV
36
Power frequency withstand test voltage, 1 minute
kV
70
Lightning impulse test voltage (1.2/50 µs full wave)
kV
170
Rated frequency
Hz
50/60
Max. rated primary voltage
kV
36/√3
Secondary thermal limit current for measuring winding
A
7
Rated voltage factor /8h
1.9
Secondary thermal limit current for Earth – fault winding
A
4
Secondary Voltage
V
100/√3;110/√3;220/√3
Max number of cores
  3
Accuracy class measuring / protection
0.2-0.5-1 /3P -6P
Rated output
 15-100 VA
Category:

Description

VMI

Type
VM36-1
e1
300
e2
150
e3
46
e4
L
395
b1
190
b2
220
h
390
h1
102
d
14
d1
d2

Dimensions in mm

 

Download Catalog