24 kV – 24 kV current transformer

Instrument current
Transformers, indoor,
Cast-Resin Insulated

On Request:
Constructions with capacitive layer
Ribs on the top for increasing creepage distance(AMS24-R,AM24-R,AMG24-R)
Ribs height 35 mm
* Change over: with multi-purpose transformers it is possible to work with several primary currents. In principle, the change over can be made from the primary as well as from the secondary side.
(Secondary tapping; for instance 800-1000/5A)
Type
 
AMS24
AM24
AMG24
Highest voltage for equipment
kV
24
24
24
Power frequency withstand test voltage, 1 minute
kV
50
50
50
Lightning impulse test voltage (1.2/50 m s full wave)
kV
125
125
125
Rated frequency
Hz
50/60
50/60
50/60
Rated primary current
A
5-400
5-2500
5-2500
Primary reconnection*1:2
A
2 x 200
2 x 600
2 x 600
Secondary current
A
5 or 1
5 or 1
5 or 1
Max. rated continuous thermal current x In
A
1.2
1.2
1.2
Rated short time thermal current Ith in1 sec.(100-1000) x In
Max.kA
40
60
60
Rated dynamic current Idyn = 2.5 x Ith
Max.kA
100
120
120
Max. number of cores
1
3
3
Accuracy class measuring / protection
0.2-0.5-1/5P -10P
Rated output (measuring / protection)
5-60VA/1-30 VA
Instrument security factor (measuring; FS5, FS10)/ Accuracy limit factor (protection; P5-P30)
Category:

Description

Type
AMS24
AM24
AMG24
e1
210
280
380
e2
120
120
120
e3
0
32
32
e4
45
80
130
L
292
362
462
b1
148
148
148
b2
178
178
178
h
290
285
285
d
14
14
14
Primary ≥ 1500 A

Dimensions in mm

Download Catalog